Purpose

Polls a local NUT (Network UPS Tools) daemon for battery status and publishes power state transitions onto the MQTT bus. When the UPS runs below a configured critical-runtime threshold, triggers a graceful shutdown of the host.

Key files

  • vigilar/ups/monitor.pyUPSMonitor: NUT client, status parser, transition detection, MQTT publisher
  • vigilar/ups/shutdown.pyShutdownSequence: publishes SYSTEM_SHUTDOWN and executes the OS shutdown
  • vigilar/ups/__init__.py

MQTT topics

Subscribes: none Publishes:

  • vigilar/ups/status (every poll; status, battery charge %, runtime seconds, input voltage, load %)
  • vigilar/ups/power_loss (transition OL -> OB/LB)
  • vigilar/ups/restored (transition back to OL)
  • vigilar/ups/low_battery (charge below low_battery_threshold_pct)
  • vigilar/ups/critical (runtime below critical_runtime_threshold_s, triggers shutdown)
  • vigilar/system/shutdown (published by ShutdownSequence)

Database tables

  • events — writes POWER_LOSS, POWER_RESTORED, LOW_BATTERY rows via insert_event
  • system_events — writes operator-facing notices ("Power loss detected — running on battery", critical shutdown messages)

Depends on

  • External NUT daemon reachable at [ups] nut_host:nut_port via the pynut2 client
  • storageinsert_event, insert_system_event

Consumed by

  • events — classifies vigilar/ups/* into POWER_LOSS / LOW_BATTERY / POWER_RESTORED
  • alerts — receives those classified events through rule actions
  • main supervisor — reacts to SYSTEM_SHUTDOWN so all subsystems can drain cleanly

Notes

The critical shutdown trigger fires when the UPS is not online AND battery.runtime < ups.critical_runtime_threshold_s AND no shutdown has already been triggered. The low-battery alert fires when battery.charge < ups.low_battery_threshold_pct while off mains. NUT reconnection uses exponential backoff capped at 120 seconds, so the monitor survives a temporary NUT restart without the supervisor having to restart it.